Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 50

Advertising
background image

3-14

Programming and Parameters

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

UTILITY

Diagnostic

214

[Start Inhibit]

A set of bits displaying the interlocks that inhibit the Converter from starting.

Bit 0 (Ac Low Volt) is set when the average AC line voltage is less than the limit in parameter 112 - [Low Vac Lmt].

Bit 1 (Ac High Volt) is set when the average AC line voltage exceeds the limit in parameter 114 - [High Vac Lmt].

Bit 2 (Ac Low Freq) is set when the AC line frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].

Bit 3 (Ac High Freq) is set when the AC line frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].

Bit 4 (Single Phase) is set when an input phase is missing.

Bit 5 (Phased ACB) is set when an input phase voltage is phased ACB and parameter 051 - [Option Select] Bit 0 (AutoPhaseRot)
is not enabled.

Bit 6 (DC Link Low) is set when DC Link voltage is too low to close the precharge bypass contactor.

Bit 7 (High dv/dt) is set when DC Link dv/dt is too high to close the precharge bypass contactor.

Bit 8 (Pchg Open) is set when the precharge bypass contactor is open and manual sequencing is selected.

Bit 9 (PWM Not Sync) is set when Par 051 - [Option Select] Bit 3 (PWM SyncRecv) is turned on and synchronization is not completed.

Bit 10 (Reqst Maintd) is set after a fault if the enable is not turned off. Restart requires a rising edge.

Bit 11 (High DC Link) is set when Run On PwrUp is selected in parameter 50 - [Start Config] and the DC Link is greater than
1.44 times the value in parameter 114 - [High Vac Lmt]. On a 480 volt unit, parameter 114 - [High Vac Lmt] defaults to “528” so
inhibit Bit 11 (High DC Link) defaults to 760 volts.

Bit 15 (Faulted) is set when the Converter is faulted.

220

[Fault Frequency]

Displays the AC line frequency at the time of the fault.

Default:

Min/Max:
Units:

Read Only

0.0/100.0
0.1 Hz

221

[Fault Amps R]

Displays phase R peak current at the time of the fault.

Default:

Min/Max:
Units:

Read Only

-3276.7/+3276.7
0.1 Amps

222

[Fault Amps S]

Displays phase S peak current at the time of the fault.

Default:

Min/Max:
Units:

Read Only

-3276.7/+3276.7
0.1 Amps

223

[Fault Amps T]

Displays phase T peak current at the time of the fault.

Default:

Min/Max:
Units:

Read Only

-3276.7/+3276.7
0.1 Amps

224

[Fault Amps Q]

Displays the real current at the time of the fault.

Default:

Min/Max:
Units:

Read Only

-3276.7/+3276.7
0.1 Amps

225

[Fault Amps D]

Displays the reactive current at the time of the fault.

Default:

Min/Max:
Units:

Read Only

-3276.7/+3276.7
0.1 Amps

226

[Fault Volts RS]

Displays the RMS line-to-line voltage between phase R and S at the time of the fault.

Default:

Min/Max:
Units:

Read Only

0.0/3276.7
0.1 Vac

227

[Fault Volts ST]

Displays the RMS line-to-line voltage between phase S and T at the time of the fault.

Default:

Min/Max:
Units:

Read Only

0.0/3276.7
0.1 Vac

228

[Fault Volts TR]

Displays the RMS line-to-line voltage between phase T and R at the time of the fault.

Default:

Min/Max:
Units:

Read Only

0.0/3276.7
0.1 Vac

229

[Fault Volts Vdc]

Displays the DC Link voltage at the time of the fault.

Default:

Min/Max:
Units:

Read Only

0.0/3276.7
0.1 Vdc

Fil

e

Gr

oup No.

Parameter Name & Description

Values

Bit
Definition

Fault

ed

High DC Link

Re

qst Ma

in

td

PWM Not

Sy

nc

Pc

hg Open

High dv

/d

t

DC Link

Lo

w

Ph

ased

A

C

B

Single Pha

se

Ac

High

F

req

Ac

Lo

w

F

req

Ac

High

V

olt

Ac

Lo

w

V

olt

Default

0

x

x

x

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled
x = Reserved

Read Only