Programming and Parameters

3-11

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

Dynamic Control File

Fil

e

Gr

oup No.

Parameter Name & Description

Values

D

Y

N

A

M

IC CO

N

T

R

O

L

Current

Loop

150

[Reduce Ilmt Sel]

Enables the use of a reduced current limit when in overload.

“Disabled” = The Converter current limit is always the value in parameter 100 -
[Active I Lmt].

“Enabled” = The Converter current limit will switch to the value set by parameter
101 - [Active OL I Lmt] when in overload.

Default:

Options:

1

0
1

“Disabled”

“Disabled”
“Enabled”

151

[Active I Cmd]

Displays the commanded active current.

Default:

Min/Max:
Units:

Read Only

-3276.7/+3276.7
0.1 Amps

152

[Inductance]

Sets the input filter inductance. When set to non-zero, this value is used to
calculate the tuning coefficients for the current loop CML Ki and Kp.

Default:

Min/Max:
Units:

Rated µH

0/32767 µH
1 µH

153

[CML Bandwidth]

Sets the Current Minor Loop bandwidth. When set to non-zero, this value is
used to calculate the tuning coefficients for the current loop CML Ki and Kp.

Default:

Min/Max:
Units:

1500 Rad/sec

0/4000 Rad/sec
1 Rad/sec

154

[CML Damping]

Sets the Current Minor Loop damping. When set to non-zero, this value is used
to calculate the tuning coefficients for the current loop CML Ki and Kp.

Default:

Min/Max:
Units:

1.6

0.5/5.0
None

155

[CML Ki]

Tunes the integral gain of the current loop.

Default:

Min/Max:
Units:

Drive Size Dependent

0/32767
None

156

[CML Kp]

Tunes the proportional gain of the current loop.

Default:

Min/Max:
Units:

Drive Size Dependent

0/32767
None

157

[PF Bandwidth]

Sets the bandwidth of the current regulator maintaining the desired power factor.
This is used only when parameter 051 - [Option Select] Bit 1 (Unbal V Comp) is
set to "1" to enable unbalanced voltage compensation.

Default:

Min/Max:
Units:

Drive Size Dependent

0/4000
None

158

[Reactive I Lmt]

Displays the calculated reactive current limit.

Default:

Min/Max:
Units:

Read Only

0.0/3000.0
0.1 Amps

159

[Reactive I Cmd]

Displays the commanded reactive current.

Default:

Min/Max:
Units:

Read Only

-3000.0/+3000.0
0.1 Amps

V

o

lta

g

e Loop

160

[Voltage Loop Sel]

Selects the operation of the voltage loop.

“Optimize Ref” = Vdc reference is calculated to minimize switching losses,
based on the measured AC Line voltage and the minimum voltage required by
the Inverter.

“Manual Ref” = The value set by parameter 060 - [DcLink Reference] is used for
Vdc reference.

“Regen Only” = Reserved for future.

“Open Loop” = The Converter outputs a sinusoidal voltage synchronized to the
AC line with an amplitude set by parameter 063 - [Modulation Index]. This
feature requires a password to operate.

Default:

Options:

0

0
1
2
3

“Optimize Ref”

“Optimize Ref”
“Manual Ref”
“Regen Only”
“Open Loop”

161

[DcLink Command]

Displays the commanded DC Link voltage.

Default:

Min/Max:
Units:

Read Only

0.0/1225.0
0.1 Vdc