Resetting converter faults, Resetting converter faults -18 – Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 36

Advertising
background image

2-18

Start Up

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

1. Rather than selecting Parameters, use the Up arrow to select

“Diagnostics” and press the Enter key.

2. The HIM then displays the Diagnostics menu. With “Events” selected,

press the Enter key.

3. The HIM then displays the Diag: Events menu. With “View Event

Queue” selected, press the Enter key.

4. The HIM then displays the Event queue where the specific fault text is

displayed. In this example screen, the Converter faulted because the AC
was lost and power dip ride through was not enabled.

Resetting Converter Faults

In most cases, faults in the Converter are reset by resetting the Inverter. If
the condition causing the fault is still present, then a second fault is
generated and recorded in the fault queue. The only exception is a
checksum fault in the Converter. A checksum fault in the Converter is reset
by doing a reset defaults in the Converter, and then reset the fault in the
Inverter.

Clearing the fault queue in the Inverter does not affect the event queue in the
Converter. The Converter event queue is cleared independently of the
Inverter fault queue.

Port 6 Device

PowerFlex 700AC

Main Menu:

Diagnostics

Parameter
Device Select

Port 6 Device

PowerFlex 700AC

Diagnostics:

Events

Status Info
Device Version

Port 6 Device

PowerFlex 700AC

Diag: Events

View Event Queue

Clear Events
Clr Event Queue

Port 6 Device

PowerFlex 700AC

EvtQ#1:

E#

40

AC Line Lost
Accum:

0:00:00.001