Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 63

Advertising
background image

Troubleshooting

4-3

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

PWM Sync Lost

46

PWM Carrier synchronization was lost.

Verify wiring of carrier synchronization
cable.

Variations in the AC Line Faults

Ac Low Voltage

50

AC line voltage was below the configured limit for the configured
time.

Verify proper input line voltage is present.

Ac High Voltage

51

AC line voltage exceeded the configured limit for the configured
time.

Verify proper input line voltage is present.

Ac Low Frequency

52

AC line frequency was below the configured limit for the
configured time.

Verify proper input line voltage is present.

Ac HighFrequency

53

AC line frequency exceeded the configured limit for the configured
time.

Verify proper input line voltage is present.

Ac High dFdt

54

Change in line frequency exceeded the configured limit.

Verify proper input line voltage is present.

Ac I Imbalance

55

AC current balance exceeded the configured limit for the
configured time.

Verify proper input line voltage is present.

Ac V Imbalance

56

AC voltage balance exceeded the configured limit for the
configured time.

Verify proper input line voltage is present.

DcLink Low Volt

57

DC link voltage was below the precharge open level.

Verify proper input line voltage is present.

Ride Thru Expire

58

Power dip ride through expired with precharge open.

Verify proper input line voltage is present.

Ride Thru Expire

59

Power dip ride through expired with precharge closed.

Verify proper input line voltage is present.

Overload Faults

IT Over Load

60

Operating current levels exceeded the rated overload.

Verify proper input line voltage is present.

Ambnt Over Temp

61

Measured ambient temperature exceeded the maximum limit.

Base Over Temp

62

IGBT base temperature exceeded the maximum limit.

Verify required drive cooling is present.

Junct Over Temp

63

IGBT junction temperature exceeded the maximum limit.

Verify required drive cooling is present.

Ntc Range Low

64

NTC temperature outside below rated temperature range.

Check for open or shorted NTC device.

Ntc Range High

65

NTC temperature outside above rated temperature range.

Check for open or shorted NTC device.

PS1 Fan Loss

66

Power Structure 1 detected a circulating fan was lost.

(2)

Verify internal circulating fans are turning.

PS1 Reactor Temp

67

Power Structure 1 detected the reactor thermal switch opened.

(2)

Verify reactor cooling fans are turning.

PS2 Fan Loss

68

Power Structure 2 detected a circulating fan was lost.

(3)

Verify internal circulating fans are turning.

PS2 Reactor Temp

69

Power Structure 2 detected the reactor thermal switch opened.

(3)

Verify reactor cooling fans are turning.

Input Filter Fault

FiltCap Contactr

70

The detected state (open/closed) of the input filter capacitor bank
contactor does not match the commanded state.

Verify wiring of filter capacitor contactor.

Stand Alone Unit (DPI MASTER) Faults

Port 1 Adapter

71

The communication card has detected a fault on the network.

(4)

Check DPI device event queue and
corresponding fault information for the
device.

Port 2 Adapter

72

The communication card has detected a fault on the network.

(4)

Port 3 Adapter

73

The communication card has detected a fault on the network.

(4)

Port 4 Adapter

74

The communication card has detected a fault on the network.

(4)

Port 5 Adapter

75

The communication card has detected a fault on the network.

(4)

Port 6 Adapter

76

The communication card has detected a fault on the network.

(4)

Port 1 DPI Loss

81

The DPI communication to a peripheral was lost.

(4)

1. If adapter was not intentionally

disconnected, check wiring to the port.
Replace wiring, port expander,
adapters, Main Control Board, or
complete Converter as required.

2. Check HIM connection.

3. If an adapter was intentionally

disconnected and the [Logic Mask] bit
for that adapter is set to “1,” this fault
will occur. To disable this fault, set the
[Logic Mask] bit for the adapter to “0.”

Port 2 DPI Loss

82

The DPI communication to a peripheral was lost.

(4)

Port 3 DPI Loss

83

The DPI communication to a peripheral was lost.

(4)

Port 4 DPI Loss

84

The DPI communication to a peripheral was lost.

(4)

Port 5 DPI Loss

85

The DPI communication to a peripheral was lost.

(4)

Port 6 DPI Loss

86

The DPI communication to a peripheral was lost.

(4)

(1)

See

page 4-1

for a description of fault types.

(2)

These faults only apply to Frame 3 power structures.

(3)

These faults are reserved for future use.

(4)

These faults only apply when operating the Active Converter as a Stand Alone unit (DPI Master).

Fault

No.

Type

(1)

Description

Action