Programming and Parameters

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

UTILITY

Fa

u

lt

Q

u

eu

e

247

[Fault 3 Code]

Displays the most third recent fault code detected.

Default:

Min/Max:
Units:

Read Only

0/65535
0

248

[Fault 3 Time]

Displays the time stamp for the most third recent fault detected.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hrs

249

[Fault 4 Code]

Displays the most fourth recent fault code detected.

Default:

Min/Max:
Units:

Read Only

0/65535
0

250

[Fault 4 Time]

Displays the time stamp for the most fourth recent fault detected.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hrs

260

[Alarm Config]

A set of bits to enable/disable alarm conditions that will initiate a Converter alarm.

Bit 0 (Ac Low Volt) sets an alarm when the average AC line voltage is less than the limit in parameter 112 - [Low Vac Lmt].

Bit 1 (Ac High Volt) sets an alarm when the average AC line voltage exceeds the limit in parameter 114 - [High Vac Lmt].

Bit 2 (Ac Low Freq) sets an alarm when the AC line frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].

Bit 3 (Ac High Freq) sets an alarm when the AC line frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].

Bit 4 (Ac High dFdt) sets an alarm when the AC line frequency is changing faster than the limit in parameter 135 - [AC Maximum
dF/dt].

Bit 5 (I Imbalance) sets an alarm when the phase current imbalance exceeds the limit in parameter 103 - [I Imbalance Lmt].

Bit 6 (V Imbalance) sets an alarm when the phase voltage imbalance is greater than the limit in parameter 116 - [V Imbalance
Lmt].

Bit 7 (IT Overload) sets an alarm when the Overload counter is greater than 90%.

Bit 8 (Ambient Temp) sets an alarm when the ambient temperature exceeds the limit in parameter 120 - [Ambnt Temp Alrm].

Bit 9 (Base Temp) sets an alarm when the IGBT base temperature exceeds the limit in parameter 122 - [Base Temp Alrm].

Bit 10 (Junction Temp) sets an alarm when the IGBT junction temperature exceeds the limit in parameter 124 - [Junct Temp
Alrm].

Bit 11 (Coldplate Temp) sets an alarm when the coldplate temperature is less than the limit in parameter 126 - [CldPlt Temp
Alrm].

Bit 12 (PWM SyncLoss) sets an alarm when PWM carrier synchronization is lost.

Bit 15 (Start Inhibit) sets an alarm when one or more start inhibits are present.

Fil

e

Gr

oup No.

Parameter Name & Description

Values

Bit
Definition

Sta

rt I

nhibit

PWM Sy

ncLo

ss

Coldplat

e T

emp

Junc

tion

T

emp

Base

T

emp

Ambient

T

emp

IT Ov

er

lo

ad

V I

m

balan

ce

I Imb

al

ance

Ac High dFdt

Ac High F

req

Ac Lo

w

F

req

Ac High V

olt

Ac Lo

w

V

olt

Default

1

x

x

1

0

1

1

1

1

1

1

1

1

1

1

1

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled
x = Reserved