Monitor file, Monitor file -4 – Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 40

Advertising
background image

3-4

Programming and Parameters

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

Monitor File

Fil

e

Gr

oup No.

Parameter Name & Description

Values

MO

NIT

O

R

Curr

ent

001

[Rated Amps]

When operating as a Coupled unit, displays the same rated current as the inverter
as the voltage class is changed.

Default:

Min/Max:
Units:

Read Only

0.0/3000.0
0.1 Amps

002
003
004

[Input Current R]
[Input Current S]
[Input Current T]

Displays the measured RMS phase currents.

Default:

Min/Max:
Units:

Read Only

0.0/3000.0
0.1 Amps

005

[Ground Current]

Displays the measured ground current.

Default:

Min/Max:
Units:

Read Only

0.0/3000.0
0.1 Amps

006

[Active Current]

Displays the measured active current. Positive values are motoring, negative values
are regeneration.

Default:

Min/Max:
Units:

Read Only

-3000.0/+3000.0
0.1 Amps

007

[Reactive Current]

Displays the measured reactive current. Positive is lagging, negative is leading
power factor.

Default:

Min/Max:
Units:

Read Only

-3000.0/+3000.0
0.1 Amps

008

[I Imbalance]

Displays the current imbalance calculated between phases R, S, and T.

Default:

Min/Max:
Units:

Read Only

0.0/100.0
0.1%

009

[IT Overload]

Displays the accumulated IT overload. The Converter allows 110% for 60 seconds
and 150% for 3 seconds. Operating beyond these ratings will result in this
accumulator counting up to 100.0% and the generation of a fault. An alarm is turned
on when this parameter reaches 90.0 %, at which time the current limit can be
reduced until this parameter integrates down to 50.0%.

Default:

Min/Max:
Units:

Read Only

0.0/100.0
0.1%

V

o

ltag

e

010

[Rated Volts]

When operating as a Coupled unit, displays the same rated voltage as the inverter
as the voltage class is changed.

Default:

Min/Max:
Units:

Read Only

0.0/690.0
0.1 Vac

011
012
013

[Input Voltage RS]
[Input Voltage ST]
[Input Voltage TR]

Displays the measured AC line-to-line RMS voltage.

Default:

Min/Max:
Units:

Read Only

0.0/760.0
0.1 Vac

014

[DcLink Voltage]

Displays the measured DC Link Voltage.

Default:

Min/Max:
Units:

Read Only

0.0/1225.0
0.1 Vdc

015

[DcLink Ripple]

Displays the measured voltage ripple on the DC Link.

Default:

Min/Max:
Units:

Read Only

0.0/1225.0
0.1 Vdc

016

[V Imbalance]

Displays the voltage imbalance calculated between phases R, S, and T.

Default:

Min/Max:
Units:

Read Only

0.0/100.0
0.1%

Po

w

er

&

T

im

e

020

[Rated Power]

Displays the Converter’s rated power.

Default:

Min/Max:
Units:

Read Only

0.00/3000.00
0.01 kW

021

[AC Line kW]

Displays the power flowing to and from the AC Line. Positive values indicate power
is from the line. Negative values indicate power is returned to the line.

Default:

Min/Max:
Units:

Read Only

-3000.0/+3000.0
0.1 kW

022

[Motoring kWh]

Displays the accumulated positive kWh. This parameter may be reset with
parameter 200 - [Reset Meters].

Default:

Min/Max:
Units:

Read Only/Reset

0.0/429496729.5
0.1 kWh

023

[Regen kWh]

Displays the accumulated negative kWh. This parameter may be reset with
parameter 200 - [Reset Meters].

Default:

Min/Max:
Units:

Read Only/Reset

0.0/429496729.5
0.1 kWh