Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 46

Advertising
background image

3-10

Programming and Parameters

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

LIMIT CONFIG

A

C

Li

ne V

o

lta

g

e 117 [V Imbalance Time]

Sets the time delay in detecting a voltage imbalance between phases. A fault or
alarm may be generated if the calculated imbalance is greater than the limit set
by parameter 116 - [V Imbalance Limit] for this amount of time.

Default:

Min/Max:
Units:

1.0 Sec

1.0/10.0 Sec
0.1 Sec

Te

m

p

er

at

u

re

120

[Ambnt Temp Alrm]

Sets the alarm threshold for the maximum ambient temperature.

Default:

Min/Max:
Units:

60.0°C

30.0/105.0°C
0.1°C

121

[Ambnt Temp Trip]

Displays the fault threshold for the maximum ambient temperature.

Default:

Min/Max:
Units:

Read Only

40.0/150.0
0.1°C

122

[Base Temp Alrm]

Sets the alarm threshold for the maximum IGBT base temperature.

Default:

Min/Max:
Units:

70.0°C

30.0/125.0°C
0.1°C

123

[Base Temp Trip]

Displays the fault threshold for the maximum IGBT base temperature.

Default:

Min/Max:
Units:

Read Only

75.0/160.0
0.1°C

124

[Junct Temp Alrm]

Sets the alarm threshold for the maximum IGBT junction temperature.

Default:

Min/Max:
Units:

85.0°C

75.0/150.0°C
0.1°C

125

[Junct Temp Trip]

Displays the fault threshold for the maximum IGBT junction temperature.

Default:

Min/Max:
Units:

Read Only

75.0/175.0

0.1°C

126

[CldPlt Temp Alrm]

Sets the alarm threshold for the minimum coldplate temperature.

Default:

Min/Max:
Units:

40.0°C

10.0/80.0°C
0.1°C

Frequen

cy

130

[PWM Frequency]

Sets the PWM carrier frequency. The value is entered in kHz. When the power
structure allows more than one setting for the carrier frequency, the power must
be cycled off/on to have the new value take effect.

Default:

Min/Max:
Units:

Rated kHz

Set by the power structure
1 kHz

131

[AC Low Freq Lmt]

Sets the low frequency limit used by parameter 132 - [AC Low Freq Time].

Default:

Min/Max:
Units:

29.0 Hz

27.0/93.0 Hz
0.1 Hz

132

[AC Low Freq Time]

Sets how long the line frequency must be less than the limit set by parameter
131 - [AC Low Freq Lmt] before a fault is generated.

Default:

Min/Max:
Units:

5.0 Sec

0.1/10.0 Sec
0.1 Sec

133

[AC High Freq Lmt]

Sets the high frequency limit used by parameter 134 - [AC High Freq Time].

Default:

Min/Max:
Units:

91.0 Hz

27.0/93.0 Hz
0.1 Hz

134

[AC High Freq Time]

Sets how long the line frequency must be greater than the limit set by parameter
133 - [AC High Freq Lmt] before a fault is generated.

Default:

Min/Max:
Units:

5.0 Sec

0.1/10.0 Sec
0.1 Sec

135

[AC Maximum dF/dt]

Sets the maximum dF/dt that the AC converter will allow. A change in frequency
greater than this may generate a fault.

Default:

Min/Max:
Units:

10.0 Hz/sec

0.1/30.0 Hz/sec
0.1 Hz/sec

Fil

e

Gr

oup No.

Parameter Name & Description