Cip messages, Cip messages -7 – Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual
Page 25

Start Up
2-7
PowerFlex 700L Active Converter Power Module User Manual
CIP Messages
Parameters in the Converter may be accessed by a Logix processor using a
CIP message block. To read or write a parameter value you must
respectively perform a Get Attribute Single or Set Attribute Single message
to the DPI Parameter Object (Class 0x93). The Converter is in DPI Port 6,
so the instance is 22528 plus the parameter number. The value of the
parameter is accessed through Attribute 0x9 or 0xA. The example shown
below reads the value of Converter parameter 30 - [Ambient Temp].
Class Code
Instances
Attributes
Hexadecimal
Decimal
0x93
147
Instances (Hex.)
(Dec.)
Device
0x0000 – 0x3FFF
0 – 16383
Host
0x4000 – 0x43FF
16384 – 17407
Adapter
0x4400 – 0x47FF
17408 – 18431
DPI Port 1
0x4800 – 0x4BFF
18432 – 19455
DPI Port 2
0x4C00 – 0x4FFF
19456 – 20479
DPI Port 3
0x5000 – 0x53FF
20480 – 21503
DPI Port 4
0x5400 – 0x57FF
21504 – 22527
DPI Port 5
0x5800 – 0x5BFF
22528 – 23551
DPI Port 6
ID
Rule
Name
Data Type
Description
0x9
Get/Set
Parameter Value
Various
Value in NVS
0xA
Get/Set
Parameter Value
Various
Value in RAM