Programming and Parameters

3-5

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

MO

NIT

O

R

Po

w

er

&

T

im

e

024

[Life Time kWh]

Displays the lifetime accumulated kWh. This parameter cannot be reset.

Default:

Min/Max:
Units:

Read Only

0.0/429496729.5
0.1 kWh

025

[Elapsed Run Time]

Displays the accumulated amount of time the Converter has been in run. This
parameter can be reset with parameter 200 - [Reset Meters].

Default:

Min/Max:
Units:

Read Only/Reset

0.0000/429496.7295
0.0001 Hr

026

[Life Run Time]

Displays the accumulated amount of time the Converter has been in run. This
parameter cannot be reset.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hr

027

[Life Power Time]

Displays the accumulated amount of time the Converter has been powered up. This
parameter cannot be reset to zero.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hr

028

[Life Pwr Cycles]

Displays the accumulated number of times the Converter has been powered up.
This parameter cannot be reset to zero.

Default:

Min/Max:
Units:

Read Only

0/4294967295
None

Te

m

p

er

at

u

re

030

[Ambient Temp]

Displays the measured ambient temperature of the Converter.

Default:

Min/Max:
Units:

Read Only

-40.0/+150.0
0.1°C

031

[IGBT Base Temp]

Displays the measured IGBT base temperature.

Default:

Min/Max:
Units:

Read Only

-40.0/+150.0
0.1°C

032

[IGBT Junction Temp]

Displays the calculated IGBT junction temperature.

Default:

Min/Max:
Units:

Read Only

-40.0/+150.0
0.1°C

Frequ

enc

y

040

[Line Frequency]

Displays the measured line frequency.

Default:

Min/Max:
Units:

Read Only

0.0/90.0
0.1 Hz

041

[Min Line Freq]

Latches and displays the minimum measured line frequency. The minimum is held
for the time set with parameter 43 - [Min Max Persist].

Default:

Min/Max:
Units:

Read Only

0.0/90.0
0.1 Hz

042

[Max Line Freq]

Latches and displays the maximum measured line frequency. The maximum is held
for the time set with parameter 43 - [Min Max Persist].

Default:

Min/Max:
Units:

Read Only

0.0/90.0
0.1 Hz

043

[Min Max Persist]

Sets the persistence time of the minimum and maximum measured line frequency.
A value of zero results in the minimum and maximum never being reset.

Default:

Min/Max:
Units:

10.0 Sec

0.0/60.0 Sec
0.1 Sec

044

[Change Line Freq]

Displays the measured change in line frequency in Hz/sec.

Default:

Min/Max:
Units:

Read Only

0.0/20.0
0.1 Hz/s

Fil

e

Gr

oup No.

Parameter Name & Description

Values