Chapter 4, Troubleshooting, Faults and alarms – Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 61: Manually clearing faults, Fault descriptions

Advertising
background image

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

Chapter

4

Troubleshooting

This chapter provides information to guide you in troubleshooting the
PowerFlex 700L Active Converter Power Module. Included is a listing and
description of faults (with possible solutions, when applicable) and alarms.

Faults and Alarms

A fault is a condition that stops the Converter. There are two fault types.

An alarm is a condition that, if left untreated, may stop the Converter. All
alarms are configurable using parameter 260 - [Alarm Config].

Manually Clearing Faults

Fault Descriptions

The PowerFlex 700L Active Converter Power Module tests for many
different conditions to detect abnormal operation. The following Active
Converter faults are listed by name, fault code number, type, description of
the condition, and corrective action required by the user where applicable.

With the ability to connect larger frame size power structures in parallel,
each structure has independent fault detection to indicate the source of the
problem (for example, PS1 for Primary Converter and PS2 for Secondary
Converter).

For information on …

See page…

Faults and Alarms

4-1

Manually Clearing Faults

4-1

Fault Descriptions

4-1

Clearing Alarms

4-4

Alarm Descriptions

4-4

Type

Fault Description

Reserved for future.

Non-Resettable

This type of fault normally requires drive or motor repair. The cause of
the fault must be corrected before the fault can be cleared. The fault will
be reset on power up after repair.

User Configurable

These faults can be enabled/disabled to annunciate or ignore a fault
condition.

Step

Key(s)

1. Press Esc to acknowledge the fault. The fault information will be removed so that

you can use the HIM.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault by one of these methods.

Press Stop

Cycle drive power

Set parameter 239 - [Fault Clear] to “1 = Clear Faults.”

“Clear Faults” on the HIM Diagnostic menu.

Esc