2-2

Super Remote Meter Interface (RMI) Board

2.2

Terminal Strip Signals

The following signals are available at the terminal strip. Refer to figure 3.21 for
terminal identification.

2.2.1 Digital Inputs

Four 24 volt DC digital inputs provide additional speed reference options. The inputs
are active high. A 24 VDC supply is provided by the RMI board for use with the digital
inputs. The supply is short circuit- and overvoltage-protected. See figure 2.2.

Important: This supply should not be used as an external supply for anything other

than the four digital inputs.

2.2.2 Digital Outputs

Four 24 volt digital outputs are turned on and off as a result of data comparisons in the
drive. Refer to table 3.9 and chapter 4 for the related parameters and programming
information.

All digital outputs are source-driven (active high with common ground) and short
circuit-protected. Each output has an adjustable time delay that can be programmed
as an on-delay or an off-delay. An option to select an external 24 volt supply for
increased current capability at the outputs is jumper-selectable as shown in table 2.1.
Refer to figure 2.1 for the jumper location.

Figure 2.2 – Digital Input Circuit

,Q 

,Q 

,Q 

 9'&

,Q 

Table 2.1 – Jumper Selections for Digital Output Supply Source

Jumper Selection

24VDC Supply Source

Output Result

24 V INT

Internal

20mA per output

24 V EXT

External

100mA per output

Figure 2.3 – Digital Output Circuit

2SWLRQDO

([WHUQDO

 9

2XW 

2XW 

2XW 

2XW 

 9

&RPP