3-28

Super Remote Meter Interface (RMI) Board

Step 4.

Install the RMI Board in the Keypad Bracket

Step 4.1 Remove the RMI board from its anti-static wrapper and verify that the

jumper settings are correct. Refer to figure 2.1 for jumper locations and
appendix A for jumper settings.

Step 4.2 Align the key on the Regulator board’s 34-conductor ribbon cable connector

with the slot in the RMI board’s connector. Press the ribbon cable connector
in until it locks into position.

Step 4.3 Align the RMI board on the four mounting tabs on the keypad bracket. Make

sure that the ribbon cable is not pinched between the keypad bracket and
the RMI board.

Step 4.4 Fasten the RMI board to the right side of the keypad bracket using the two

metal M3 screws and lock washers for proper grounding. Fasten the left
side using the two 6-32 screws and lock washers for proper grounding.

Important: You must use the lock washers to properly ground the RMI board. Improper

grounding of the RMI board can result in erratic operation of the drive.

Figure 3.14 – Drive Components and Locations (50 to 100 HP @ 460 VAC)

45

47

47

45

Keypad

Regulator
Board

Power Module
Interface Board

DC Bus

Measuring Points

+

!

ATTENTION: The RMI board contains components that are
static-sensitive. An anti-static wrist band should be worn by any person
who touches the board’s components, connectors, or wiring. Failure to
observe this precaution could result in damage to the RMI board.