Installation

3-23

Step 3.

Remove the Keypad Bracket from the Drive

See figure 3.12 (15 to 25 HP @ 460VAC) or 3.13 (25 to 60HP @ 460VAC) for part
locations.

Step 3.1 Record connections to the Regulator board terminal strip if they must be

disconnected to remove the keypad bracket.

Step 3.2 Loosen the thumb screw on the left side of the keypad bracket. Hold the

bracket on the left and lift the bracket up and to the left to separate it from
the keypad support bracket.

Important: The keypad support bracket is connected to the drive by wiring. Do not lift

the bracket out completely, because this can damage or pull out wiring.
Tie up or support the bracket to prevent damage to the wiring.

Step 3.3 Disconnect the 26-conductor Regulator board ribbon cable from the Power

Supply board (located on the right side below the keypad). You can see the
connector through the slot on the keypad support bracket. Use a small
screwdriver inserted through the slot to spread the retaining clips on the
connector to release it.

Step 4.

Install the RMI Board in the Keypad Bracket

Step 4.4 Remove the RMI board from its anti-static wrapper and verify that the

jumper settings are correct. Refer to figure 2.1 for jumper locations and
appendix A for jumper settings.

!

ATTENTION: The RMI board contains components that are
static-sensitive. An anti-static wrist band should be worn by any person
who touches the board’s components, connectors, or wiring. Failure to
observe this precaution could result in damage to the RMI board.

Figure 3.12 – RMI Board Location in 15 to 25 HP @ 460 VAC Drives

Regulator Board

RMI Board

Top View

Front View