Rockwell Automation GV3000/SE, VTAC 7 Super Remote Meter Interface Board M/N 2SI3000 M/N 2SI3000E User Manual
Page 40
 
3-26
Super Remote Meter Interface (RMI) Board
3.6
Installing the RMI Board in 50 to 100HP and 
100 to 150HP @ 460VAC Drives (GV3000/SE Drives 
Only)
Use this procedure to install the RMI board in the GV3000/SE drives with the model 
number 50R41xx, 50T41xx, 75R41xx, 75T41xx, or 125R41xx.
Unless otherwise indicated, keep all hardware that is removed. You will need it for 
reassembly. This includes screws, lock washers, and rivets.
Important: Read and understand the warning labels on the outside of the drive
before proceeding.
Step 1.
Shut Down the Drive
Step 1.1 Disconnect, lock out, and tag all incoming power to the drive.
Step 1.2 Wait five minutes for the DC bus capacitors to discharge.
Step 1.3 Remove the cover from the drive by removing the six cover screws.
Important: Read and understand the warning labels on the inside of the drive before
proceeding.
!
ATTENTION: Only qualified electrical personnel familiar with the 
construction and operation of this equipment and the hazards involved 
should install, adjust, operate, or service this equipment. Read and 
understand this manual and other applicable manuals in their entirety 
before proceeding. Failure to observe this precaution could result in 
severe bodily injury or loss of life.
ATTENTION: The drive is at line voltage when connected to incoming 
AC power. Disconnect, lock out, and tag all incoming power to the drive 
before performing the following procedure. Failure to observe this 
precaution could result in severe bodily injury or loss of life.
ATTENTION: DC bus capacitors retain hazardous voltages after input 
power has been disconnected. After disconnecting input power, wait five 
minutes for the DC bus capacitors to discharge and then check the 
voltage with a voltmeter to ensure the DC bus capacitors are discharged 
before touching any internal components. Failure to observe this 
precaution could result in severe bodily injury or loss of life.
ATTENTION: The drive contains printed circuit boards that are 
static-sensitive. An anti-static wrist band should be worn by any person 
who touches the drive’s components, connectors, or wiring. Erratic 
machine operation and damage to, or destruction of, equipment can 
result if this procedure is not followed. Failure to observe this precaution 
could result in bodily injury.