Super Remote Meter Interface (RMI) Board
9 = Speed Reached
The output is turned on when the absolute value of 
commanded speed or frequency minus actual speed or 
frequency is less than or equal to the Speed Detection 
Hysteresis Band (r.053).
Figure 4.7 – Speed Reached
100 ms
10 = Remote
The output turns on when any control source other than 
the local keypad is selected (P.000 
≠
LOCL).
100 ms
11 = Current Level 1
The output is turned on when the motor current is greater 
than or equal to Current Detection Level 1 (r.057). The 
output is turned off when the motor current is less than or 
equal to Current Detection Level 1 minus the Current 
Detection Hysteresis (r.060).
Figure 4.8 – Current Level 1, 2, and 3
100 ms
12 = Current Level 2
The output is turned on when the motor current is greater 
than or equal to Current Detection Level 2 (r.058). The 
output is turned off when the motor current is less than or 
equal to Current Detection Level 2 minus the Current 
Level Hysteresis (r.060). Refer to figure 4.8.
100 ms
13 = Current Level 3
The output is turned on when the motor current is greater 
than or equal to Current Detection Level 3 (r.059). The 
output is turned off when the motor current is less than or 
equal to Current Detection Level 3 minus the Current 
Level Hysteresis (r.060). Refer to figure 4.8.
100 ms
14 = DC Braking Active
The output turns on when DC braking is active (H.005 to 
H.018).
This is available only in volts per hertz (V/Hz) regulation.
100 ms
Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)
Selection
Description
Update Time
+
5
+