4-12

Super Remote Meter Interface (RMI) Board

9 = Speed Reached

The output is turned on when the absolute value of
commanded speed or frequency minus actual speed or
frequency is less than or equal to the Speed Detection
Hysteresis Band (r.053).

Figure 4.7 – Speed Reached

100 ms

10 = Remote

The output turns on when any control source other than
the local keypad is selected (P.000

LOCL).

100 ms

11 = Current Level 1

The output is turned on when the motor current is greater
than or equal to Current Detection Level 1 (r.057). The
output is turned off when the motor current is less than or
equal to Current Detection Level 1 minus the Current
Detection Hysteresis (r.060).

Figure 4.8 – Current Level 1, 2, and 3

100 ms

12 = Current Level 2

The output is turned on when the motor current is greater
than or equal to Current Detection Level 2 (r.058). The
output is turned off when the motor current is less than or
equal to Current Detection Level 2 minus the Current
Level Hysteresis (r.060). Refer to figure 4.8.

100 ms

13 = Current Level 3

The output is turned on when the motor current is greater
than or equal to Current Detection Level 3 (r.059). The
output is turned off when the motor current is less than or
equal to Current Detection Level 3 minus the Current
Level Hysteresis (r.060). Refer to figure 4.8.

100 ms

14 = DC Braking Active

The output turns on when DC braking is active (H.005 to
H.018).

This is available only in volts per hertz (V/Hz) regulation.

100 ms

Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)

Selection

Description

Update Time

+

5




+

+ +\VWHUHVLV U  5 6SHHG 5HIHUHQFH

+

/




+ +\VWHUHVLV U  / /HYHO U WR U