4-10

Super Remote Meter Interface (RMI) Board

r.030 Digital Input Configuration

(Continued)

8 Presets

If r.030 = 8, one of Preset Speeds P.031 to P.038 is selected by DIGIN 2 to DIGIN 4.
See table 4.4.

The RMI board's digital and relay outputs are turned on or off as a function of 20
possible comparisons. The values in r.031 through r.037 select the comparison to use
for a particular output.

Table 4.4 – Preset Speed Digital Inputs

Digital Inputs (Terminals)

Selected

Speed Reference

DIGIN 4 (44)

DIGIN 3 (43)

DIGIN 2 (42)

OFF

OFF

OFF

P.031

OFF

OFF

ON

P.032

OFF

ON

OFF

P.033

OFF

ON

ON

P.034

ON

OFF

OFF

P.035

ON

OFF

ON

P.036

ON

ON

OFF

P.037

ON

ON

ON

P.038

r.031 to r.037 Digital Output and Relay Outputs Configuration

Par.

Parameter Name

Type

Default

Step

Range

r.031

Digital Output 1 Configuration

Config.

0

1

0 to 21 (Table 4.5)

r.032

Digital Output 2 Configuration

r.033

Digital Output 3 Configuration

r.034

Digital Output 4 Configuration

r.035

Relay Output 1 (NO) Configuration

r.036

Relay Output 2 (NO/NC) Configuration

r.037

Relay Output 3 (NO/NC) Configuration

Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections

Selection

Description

Update Time

0 = Not Used

The output is always off.

N/A

1 = Running

The output is turned on when the drive is in run.

20 ms

2 = Fault

The output is turned on when there is a fault.

20 ms

3 = Aux Input 1

The output is turned on or off (time delayed) as a function
of the Aux 1 input (digital input 4). If digital input 4 is not
programmed as Aux 1, the output will be off.

100 ms