3-18

Super Remote Meter Interface (RMI) Board

Step 3.

Remove the Keypad Bracket from the Drive

Step 3.1 VTAC 7 drives: Remove the Power Module from the drive cabinet.

Step 3.2 If the drive has:

A Regulator board and terminal cover: Remove the three M4 screws from
the cover plate over the Regulator board. Remove the cover. See figure 3.8.

A terminal cover only: If you have this type of drive, this procedure is
easier to perform if you lay the drive on its side. Remove the side cover
from the drive. Use a long magnetized screwdriver to unfasten the four
screws that hold the keypad bracket in.

Step 3.3 Remove the terminal cover, which is below the keypad and fastened with

two M4 screws. See figure 3.8.

Step 3.4 Record connections to the Regulator board terminal strip if they must be

disconnected to remove the keypad bracket.

Step 3.5 VTAC 7 drives: Remove the anodized inner cover by removing the two M3

roundhead screws.

Step 3.6 Pull the keypad assembly partly out of the drive. Spread the retaining clips

on the Regulator board ribbon cable (on the right side) to disconnect it from
the Base Board. See figure 3.9.

Step 3.7 Remove the keypad bracket. Place it with the keypad down on a flat

surface. If you cannot lay it flat, tie it up to prevent damage to wiring.

Figure 3.8 – Location of Terminal Cover and Regulator Board Cover in 30 to 100HP @ 230VAC and 75 to 200 HP @ 460 VAC Drives