Programming Reference
4-11
4 = Aux Input 2
The output is turned on or off (time delayed) as a function 
of the Aux 2 input (digital input 3). If digital input 3 is not 
programmed as Aux 2, the output will be off.
100 ms
5 = Speed Level 1
The output is turned on when the absolute value of speed 
or frequency is greater than or equal to Speed Detection 
Level 1 (r.050). The output is turned off when the absolute 
value of speed or frequency is less than or equal to 
Speed Detection Level 1 minus the Speed Detection 
Hysteresis Band (r.053).
Figure 4.5 – Speed Level 1, 2, and 3
100 ms
6 = Speed Level 2
The output is turned on when the absolute value of speed 
or frequency is greater than or equal to Speed Detection 
Level 2 (r.051). The output is turned off when the absolute 
value of speed or frequency is less than or equal to 
Speed Detection Level 2 minus the Speed Detection 
Hysteresis Band (r.053). Refer to figure 4.5.
100 ms
7 = Speed Level 3
The output is turned on when the absolute value of speed 
or frequency is greater than or equal to Speed Detection 
Level 3 (r.052). The output is turned off when the absolute 
value of speed or frequency is less than or equal to 
Speed Detection Level 1 minus the Speed Detection 
Hysteresis Band (r.053). Refer to figure 4.5.
100 ms
8 = Low Speed
The output is turned on when the absolute value of speed 
or frequency is less than or equal to the Low Speed 
Detection Level (r.056). The output is turned off when the 
absolute value of speed or frequency is greater than or 
equal to the Low Speed Detection Level plus the Speed 
Detection Hysteresis Band (r.053).
Figure 4.6 – Low Speed
100 ms
Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)
Selection
Description
Update Time
+
/
+ +\VWHUHVLV U / /HYHO U WR U
+
/
H=Hysteresis (r.053), L=Level (r.056)