Programming Reference

4-11

4 = Aux Input 2

The output is turned on or off (time delayed) as a function
of the Aux 2 input (digital input 3). If digital input 3 is not
programmed as Aux 2, the output will be off.

100 ms

5 = Speed Level 1

The output is turned on when the absolute value of speed
or frequency is greater than or equal to Speed Detection
Level 1 (r.050). The output is turned off when the absolute
value of speed or frequency is less than or equal to
Speed Detection Level 1 minus the Speed Detection
Hysteresis Band (r.053).

Figure 4.5 – Speed Level 1, 2, and 3

100 ms

6 = Speed Level 2

The output is turned on when the absolute value of speed
or frequency is greater than or equal to Speed Detection
Level 2 (r.051). The output is turned off when the absolute
value of speed or frequency is less than or equal to
Speed Detection Level 2 minus the Speed Detection
Hysteresis Band (r.053). Refer to figure 4.5.

100 ms

7 = Speed Level 3

The output is turned on when the absolute value of speed
or frequency is greater than or equal to Speed Detection
Level 3 (r.052). The output is turned off when the absolute
value of speed or frequency is less than or equal to
Speed Detection Level 1 minus the Speed Detection
Hysteresis Band (r.053). Refer to figure 4.5.

100 ms

8 = Low Speed

The output is turned on when the absolute value of speed
or frequency is less than or equal to the Low Speed
Detection Level (r.056). The output is turned off when the
absolute value of speed or frequency is greater than or
equal to the Low Speed Detection Level plus the Speed
Detection Hysteresis Band (r.053).

Figure 4.6 – Low Speed

100 ms

Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)

Selection

Description

Update Time

+

/




+ +\VWHUHVLV U  / /HYHO U WR U

+

/




H=Hysteresis (r.053), L=Level (r.056)