Super Remote Meter Interface (RMI) Board

The RMI board's digital and relay outputs can be individually programmed for on-delay
or off-delay. After the regulator signals an output to turn on or off, the RMI board will
wait for the programmed time delay before the output is turned on or off.

20 = Speed Reference

The output is turned on when the absolute value of the
selected speed reference is greater than or equal to Low
Speed Detection (r.056). The output is turned off when
the absolute value of the selected speed reference is less
than the value in r.056 minus the Speed Detection
Hysteresis Band (r.053).

Figure 4.10 – Speed Reference

21 = TB Start & Stop

The output is turned on when the terminal block Start and
Stop inputs are both closed. The output is turned off
when either of these inputs is open.

r.040 to r.046 Digital Output Relay Timers

Par.

Parameter Name

Type

Default

Step

Range

r.040

Digital Output 1 Delay Time

Tunable

0 sec

0.1

–999.9 to 999.9 sec

+ on-delay values
– off-delay values

r.041

Digital Output 2 Delay Time

r.042

Digital Output 3 Delay Time

r.043

Digital Output 4 Delay Time

r.044

Relay Output 1 Delay Time

r.045

Relay Output 2 Delay Time

r.046

Relay Output 3 Delay Time

Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)

Selection

Description

Update Time

RQVWDWH

6HOHFWHG 6SHHG 5HIHUHQFH

RIIVWDWH

/

+

/ /HYHO U

+ +\VWHUHVLV U