Programming Reference

4-13

15 = Reverse Rotation

For V/Hz regulation, the output is turned on when the
drive is commanding reverse rotation. If the drive is
stopped, the output is off, regardless of the commanded
direction. If running forward, the output remains off until
the drive ramps to zero, then changes direction.

For vector regulation, the output is turned on to indicate
actual reverse rotation as detected by the pulse encoder.

100 ms

16 = Torque Level 1

The output is turned on when absolute value of torque is
greater than or equal to Torque Detection Level 1 (r.063).
The output is turned off when the absolute value of torque
is less than or equal to Torque Detection Level 1 minus
the Torque Detection Hysteresis (r.066).

Figure 4.9 – Torque Level 1, 2, and 3

100 ms

17 = Torque Level 2

The output is turned on when the absolute value of torque
is greater than or equal to Torque Detection Level 2
(r.064). The output is turned off when the absolute value
of torque is less than or equal to Torque Detection Level 2
minus the Torque Detection Hysteresis (r.066). See
figure 4.9.

100 ms

18 = Torque Level 3

The output is turned on when the absolute value of torque
is greater than or equal to Torque Detection Level 3
(r.065). The output is turned off when the absolute value
of torque is less than or equal to Torque Detection Level 3
minus the Torque Detection Hysteresis (r.066). See
figure 4.9.

100 ms

19 = Speed Regulation

For vector regulation, the output is off when the speed
loop is bypassed and on when the speed loop is enabled.

For V/Hz regulation, the output is on all the time.

100 ms

Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)

Selection

Description

Update Time

+

/