15 = Reverse Rotation
For V/Hz regulation, the output is turned on when the 
drive is commanding reverse rotation. If the drive is 
stopped, the output is off, regardless of the commanded 
direction. If running forward, the output remains off until 
the drive ramps to zero, then changes direction.
For vector regulation, the output is turned on to indicate 
actual reverse rotation as detected by the pulse encoder.
100 ms
16 = Torque Level 1
The output is turned on when absolute value of torque is 
greater than or equal to Torque Detection Level 1 (r.063). 
The output is turned off when the absolute value of torque 
is less than or equal to Torque Detection Level 1 minus 
the Torque Detection Hysteresis (r.066).
Figure 4.9 – Torque Level 1, 2, and 3
100 ms
17 = Torque Level 2
The output is turned on when the absolute value of torque 
is greater than or equal to Torque Detection Level 2 
(r.064). The output is turned off when the absolute value 
of torque is less than or equal to Torque Detection Level 2 
minus the Torque Detection Hysteresis (r.066). See 
figure 4.9.
100 ms
18 = Torque Level 3
The output is turned on when the absolute value of torque 
is greater than or equal to Torque Detection Level 3 
(r.065). The output is turned off when the absolute value 
of torque is less than or equal to Torque Detection Level 3 
minus the Torque Detection Hysteresis (r.066). See 
figure 4.9.
100 ms
19 = Speed Regulation
For vector regulation, the output is off when the speed 
loop is bypassed and on when the speed loop is enabled.
For V/Hz regulation, the output is on all the time.
100 ms
Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)
Selection
Description
Update Time
+
/