Installation

3-17

Step 1.

Shut Down the Drive

Step 1.1 Disconnect, lock out, and tag all incoming power to the drive.

Step 1.2 Wait five minutes for the DC bus capacitors to discharge.

Step 1.3 VTAC 7 drives: Open the drive’s outer cabinet door.

Important: Read and understand the warning labels on the inside of the drive before

proceeding.

Step 2.

Verify That the DC Bus Capacitors are Discharged

Step 2.1 Use a voltmeter to verify that there is no voltage at the drive’s AC input

power terminals (R/L1, S/L2, T/L3 or U/T1, V/T2, W/T3).

Step 2.2 Ensure that the DC bus capacitors are discharged. To check

DC bus potential:

a. Stand on a non-conductive surface and wear insulated gloves.

b. Use a voltmeter to measure the DC bus potential at the DC bus power

terminals shown in figure 3.7.

Figure 3.7 – DC Bus Voltage Terminals (30 to 100HP @ 230VAC and 75 to 200HP @ 460VAC)

GND

V (T2)

U (T1)

W (T3)

R

S

T

DC Bus

Volts

P (+)

N (-)