Super Remote Meter Interface (RMI) Board

Step 3.1 Remove the RMI board from its anti-static wrapper and verify that the

jumper settings are correct. Refer to figure 2.1 for jumper locations and
appendix A for jumper settings.

Step 3.2 Align the key on the Regulator board’s 34-conductor ribbon cable connector

with the slot in the RMI board’s connector. Press the ribbon cable connector
in until it locks into position.

Step 3.3 Fasten the RMI board to the drive using the screws provided.

Step 4.

Reattach the Cover

Step 4.1 Remove the tabs on the faceplate breakout panel.

Step 4.2 Reconnect the keypad/display cable to the cover.

Step 4.3 Connect the RMI wiring to the appropriate RMI terminals for your

application. Refer to section 3.9 for terminal identification.

Important: When replacing the cover on 24 to 43 A drives, check that the display

cable is reconnected to the Regulator board. You will need to fold and
route the cable under the heatsink before replacing the cover.

Step 4.4 Reattach the cover using the single faceplate screw.

Step 4.5 Reconnect all faceplate wiring.

Step 4.6 Remove the lockout and tag. Apply power to the drive. SELF will be

displayed while the drive performs power-up diagnostics.

Step 4.7 This completes the hardware installation of the RMI board. Refer to chapter

4 for the required software parameter settings for your drive.