Super Remote Meter Interface (RMI) Board
Step 4.
Install the RMI Board in the Keypad Bracket
Refer to figure 3.4 for component locations.
Step 4.1 Remove the RMI board from its anti-static wrapper and verify that the
jumper settings are correct. Refer to figure 2.1 for jumper locations and
appendix A for jumper settings.
Step 4.2 Align the key on the Regulator board’s 34-conductor ribbon cable connector
with the slot in the RMI board’s connector. Press the ribbon cable connector
in until it locks into position.
Step 4.3 Route the 26-conductor ribbon cable for the Current Feedback board out of
the side of the keypad bracket.
!
ATTENTION: The RMI board contains components that are
static-sensitive. An anti-static wrist band should be worn by any person
who touches the board’s components, connectors, or wiring. Failure to
observe this precaution could result in damage to the RMI board.
Figure 3.4 – RMI Board Location in 7.5 to 10HP Drives
Side View
Front View
Top View
RMI Board
Regulator Board
RMI Board
Current Feedback Board