Rockwell Automation GV3000/SE, VTAC 7 Super Remote Meter Interface Board M/N 2SI3000 M/N 2SI3000E User Manual

Page 62

Advertising
background image

4-4

Super Remote Meter Interface (RMI) Board

The outer loop PI regulator output is used to adjust the trim reference. The input to the
PI regulator (ERROR) is computed as:

ERROR = REFERENCE + OFFSET – FEEDBACK

Where:
OFFSET = r.020
FEEDBACK = RMI Analog Input
REFERENCE is PI regulator mode-dependent:

For Mode 1, the reference is zero.

For Mode 2, the selected speed reference is used, but the reference into the
speed summing junction is set to zero as shown in figure 4.2.

The PI regulator mode is determined by the Trim Reference Source parameter (P.014)
as shown in table 4.2. If P.014 is set to a value other than 8 or 9, the PI regulator will
remain inactive. Figure 4.2 illustrates these modes.

The outer loop PI regulator is evaluated every 20ms in the regulator. The PI regulator
is enabled only when the drive is in run. If the drive is jogged, the PI regulator will
remain reset.

Digital input 4 on the RMI board can be programmed as PI-Enable by setting r.030
(Digital Input Configuration) to 1, 3, 5, or 7. The PI regulator is then enabled only when
the drive is in run and digital input 4 is on. If r.030 is not set to 1, 3, 5, or 7, the PI
regulator is enabled whenever the drive is in run

r.020, r.021, r.022 Outer Loop PI Regulator

Par.

Parameter Name

Type

Default

Step

Range

r.020

PI Regulator Offset

Tunable

0

1

– 4095 to +4095

r.021

PI Regulator Proportional Gain

Tunable

5.00

0.01

0.10 to 50.00

r.022

PI Regulator Integral Gain

Tunable

0.05

0.01

0.00 to 10.00

Table 4.2 – Regulator Operating Modes

PI Regulator Mode

PI Regulator

Reference Used

PI Regulator

Offset Used

Feedback Used

Mode 1

(P.014 = 8)

Zero

r.020

RMI Analog Input

Mode 2

(P.014 = 9)

Selected by P.000

r.020

RMI Analog Input

Inactive

(P.014 8 or 9)

Not Used

Not Used

Not Used

Advertising