r.020, r.021, r.022 Outer Loop PI Regulator
(continued)
The RMI board provides the option to make the torque limit and current limit a function 
of the RMI analog input or the RMI frequency input, depending on r.025. When the 
RMI board is not present, there is no adjustable limit.
For vector regulation, the torque limit can be adjusted. For V/Hz regulation, the current 
limit can be adjusted. The value of r.025 determines the source for the limit. When 
r.025 = 0, the limit is set to 4095. When r.025 = 1 or 2, the limit comes from the RMI 
board. This can be the RMI analog input or the RMI frequency input. The output of the 
torque limit is normalized so that 4095 corresponds to 150%. The output of the current 
limit is normalized so that 4095 corresponds to 200%.
Figure 4.2 – PI Regulator Operating Modes
r.025 Torque or Current Limit Selection
Par.
Parameter Name
Type
Default
Step
Range
r.025
Torque/Current Limit 
Source
Config.
0
1
0 =
No adjustable limit.
1 =
Limit adjusted based on normalized 
RMI analog input.
2 =
Limit adjusted based on normalized 
RMI frequency input.