Dell PowerEdge C8000 User Manual

Page 197

Advertising
background image

Installing System Components

197

a. In a 2+0 PSU configuration, a power sled blank or a C8220 compute sled must be installed in the
adjacent unoccupied bay to maintain proper cooling airflow in the enclosure.

Table 3-1. PSU and Power Sled Support Matrix

PSU
Config

Max.
Power

Redundant
Power

Sled
Shutdown

Maintenance Conditions

4+0

5600 W Not

supported

Required Shut down all sleds in the enclosure before

removing or replacing a power sled(s).

3+1

4200 W Supported Required Shut down all sleds in the enclosure before

removing or installing a power sled(s).

2+2

2800 W Supported Not

required

Power sleds can be removed or replaced

without powering off the sled(s) in the

enclosure.

2+1

2800 W Supported Required Shut down all sleds in the enclosure before

removing or replacing the power sled with

two PSU modules capacity.

2+0

a

2800 W Not

supported

Required Shut down all sleds in the enclosure before

removing or replacing a power sled(s).

1+1

1400 W Supported Not

required

Power sled can be removed or replaced

without powering off the sled in the

enclosure.