Troubleshooting

261

• Interval 3 — If the calculated value of the PWM duty cycle is less than or

equal to 100%, the FC firmware will send a signal to the fan to operate at

the set duty cycle.

• Interval 4 — If the calculated value of the PWM duty cycle is higher than

100%, the FC firmware will send a signal to the fan to operate at 100%

duty cycle and trigger sled throttling.

• Interval 5 — If the calculated value of the PWM duty cycle is less than or

equal to 100%, the FC firmware will send a signal to the fan to operate at

the set duty cycle.

• Sixth interval — If the calculated value of the PWM duty cycle is still

higher than 100% again, the FC firmware will send a signal to the fan to

operate at 100% duty cycle and trigger sled throttling for 1 hour.

To troubleshoot the enclosure fan modules:

1 Locate the faulty fan module in the back of the enclosure.
2 Each fan module has indicators that identify a faulty fan. See Figure 1-5.
3 Remove the fan module. See "Removing a Fan Module" on page 207.
4 Examine the blades for debris. If debris is present, carefully remove it.
5 Reseat the fan module. See "Installing a Fan Module" on page 208.
6 If none of the fan indicators show a fault LED and the blade do not power

on, log into the BMC web interface and check for status messages.

7 If the problem is not resolved, install a new fan.
8 If the new fan does not operate, see "Getting Help" on page 289.