266

Troubleshooting

Fresh air

mode

Upper

non-recoverable

52 °C

(125.6

°F)

Extremely high Fan controller (FC)

firmware shuts down the

system.

NOTE:

The firmware reads

inlet temperature every 5 secs.
If the inlet temperature reaches
non-recoverable threshold, the
firmware will start to check the
power status for each sled and
initiate the sled for graceful
shutdown (pull-low 4 seconds).

Upper critical

50 °C

(122

°F)

High

Chassis status indicator

lights amber.

Upper

non-critical

48 °C

(118.4

°F)

Warning

Temperature events are

recorded in the SEL.

Table 5-6. Enclosure Air Inlet Temperature Threshold Settings

(continued)

Enclosure
Inlet
Condition

Threshold
Setting

Ambient
Temp

Threshold Level Action