Air Inlet Temperature Threshold Settings
The table below lists the enclosure’s air inlet temperature thresholds and the
different fan controller firmware actions for each threshold.
Table 5-6. Enclosure Air Inlet Temperature Threshold Settings
Enclosure
Inlet
Condition
Threshold
Setting
Ambient
Temp
Threshold Level Action
Normal
mode
Upper
non-recoverable
43 °C
(109.4
°F)
Extremely high Fan controller (FC)
firmware shuts down the
system.
NOTE:
The firmware reads
inlet temperature every 5 secs.
If the inlet temperature reaches
non-recoverable threshold, the
firmware will start to check the
power status for each sled and
initiate the sled for graceful
shutdown (pull-low 4 seconds).
Upper critical
41 °C
(105.8
°F)
High
Chassis status indicator
lights amber.
Upper
non-critical
38 °C
(100.4
°F)
Warning
Temperature events are
recorded in the SEL.
Lower
non-critical
N/A
Warning Temperature
events
are
recorded in the SEL.
Lower critical
N/A
Low
Chassis status indicator
lights amber.
Lower
non-recoverable
5 °C
(41
°F)
Extremely low Chassis status indicator
lights amber.