265

Air Inlet Temperature Threshold Settings
The table below lists the enclosure’s air inlet temperature thresholds and the

different fan controller firmware actions for each threshold.

Table 5-6. Enclosure Air Inlet Temperature Threshold Settings

Enclosure
Inlet
Condition

Threshold
Setting

Ambient
Temp

Threshold Level Action

Normal

mode

Upper

non-recoverable

43 °C

(109.4

°F)

Extremely high Fan controller (FC)

firmware shuts down the

system.

NOTE:

The firmware reads

inlet temperature every 5 secs.
If the inlet temperature reaches
non-recoverable threshold, the
firmware will start to check the
power status for each sled and
initiate the sled for graceful
shutdown (pull-low 4 seconds).

Upper critical

41 °C

(105.8

°F)

High

Chassis status indicator

lights amber.

Upper

non-critical

38 °C

(100.4

°F)

Warning

Temperature events are

recorded in the SEL.

Lower

non-critical

N/A

Warning Temperature

events

are

recorded in the SEL.

Lower critical

N/A

Low

Chassis status indicator

lights amber.

Lower

non-recoverable

5 °C

(41

°F)

Extremely low Chassis status indicator

lights amber.

Advertising