Setting the Station Address

Set the station address of the DL-PD1 with the rotary switch at the top of the DL-PD1.
The station address set here must be the same as the one set through the configuration
software of the PROFIBUS DP.

Point

The station address of the DL-PD1 cannot be set to 00, 100, or more.

Set the station address before the DL-PD1 is powered on. When the
station address is changed during operations of the DL-PD1, such
change is reflected after power has been restored to the DL-PD1.

The station address setting (Set_Slave_Adress) via PROFIBUS DP is
not supported.

Station address setting switch Setting range: 01 to 99

Default value: 11