Slot number and ID number assignment

When the sensor amplifiers are connected to the DL-PD1, slot numbers are assigned to
each sensor amplifier. When using the acyclic communication with the DP-V1 service or
diagnostic function used, the slot number is used to specify the target sensor amplifier
for communication.

Also, ID numbers are assigned to the control output and external input of each sensor
amplifier in the connection order of sensor amplifiers. ID numbers are used to identify
the control output of the sensor amplifier assigned as cyclic communication data.

(Configuration example)

Point

Slot numbers and ID numbers are automatically assigned in the
connection order for sensor amplifiers. If the number of connected
sensor amplifiers or connection order is changed, the control program
may have to be changed. Design the sensor amplifier configuration
and control program with this taken into account beforehand.

"Operation mode of DL-PD1" (page 3-6)

If the effective ID setting is changed on the GT2-100N (P), restart the
GT2-100N (P). After restarting the GT2-100N (P), the DL-PD1
recognizes the specified number of units and communication with the
units is possible.

02

...

15

01

02

...

15

01

Main

unit

Expansion unit

Sensor amplifier

DL-PD1

00

00

ID number

Slot number