1 troubleshooting, Indicator specifications, Troubleshooting -2 – KEYENCE DL-PD1 User Manual

Page 64: Indicator specifications -2, Troubleshooting, Appe ndi x

Advertising
background image

4-2

- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT2) -

Appe

ndi
x

4

4-1

Troubleshooting

Indicator Specifications

The communication status of PROFIBUS DP can be checked by checking the DL-PD1
indicators.
LED display during
normal operation

Station Failure Indicator (OFF)

Bus Failure Indicator (OFF)

Data Exchange Indicator (green)

Sensor amplifier Communication Indicator (green)

SF

BF

DE

D-bus

State

Solution

OFF

OFF

Green

Green

Operating properly.

Red

Red

OFF

OFF

Starting up

The unit enters normal state after startup

operation is complete.

Red

Red

OFF

Red

System error

Turn the power on again. If the unit does not

recover, please contact your nearest

KEYENCE office (addresses are listed at the

back of this manual).

Red

*

OFF

Green

(Flashing) Starting up

The unit enters normal state after startup

operation is complete.

Red

An error occurred in the
internal system.

Check that the DL-PD1 is properly connected

to the sensor amplifier and turn the DL-PD1 on

again.

Red

(Flashing)

Communication is tentatively

impossible.

Check that there is no noise generation source

around the DL-PD1. (If the cause is removed,

normal condition is automatically recovered.)

Red

(Flashing 4

times

repeatedly)

An incompatible sensor or
a foreign sensor amplifier
(i.e., one that cannot be
intermixed) is connected.

A current limitation error
has occurred.

Confirm the sensor amplifier configuration.

Red

OFF

Green

Green

The station address setting

switch was changed during

operation.

If it was not an intentional change, recover the

setting. Normal condition is automatically

recovered.

Red

(Flashing)

OFF

Green

Green

Warning information is

notified.

Check the sensor condition.

OFF

Red

(Flashing)

OFF

*

Wait Prm state timeout of

DL-PD1

ChkCfg state timeout of

DL-PD1

Check that the hardware configuration on the

configuration software coincides with the

actual configuration.

Check that the station address setting on the

configuration software coincides with the

station address setting on the rotary switch

of the DL-PD1.

Using the configuration software, check that

the DL-PD1 Parameters are correctly set.

OFF

OFF

Green

(Flashing)

*

Starting up

The unit enters normal state after startup

operation is complete.

OFF

OFF

OFF

OFF

Power OFF

Check that the DL-PD1 is connected to the

power source.