If a communication error occurs while using the DP-V1 service, the error codes below
appear as error responses.

* A slot number where an error occurs is stored. For example, when errors occur at

Slot 1 and 4 at the same time, 01 appears on "".
When the error at Slot 1 is resolved, 04 appears on "".

Type of error

Error_Code 1

Error_Code 2

Description

Solution

Smart Access error

0xAA

0x

*

When the smart access
function is executed, there is
a sensor which is not
compatible with the operation
command.

Check the type of sensor
amplifier connected.

Sensor busy error

0xBA

0x00

A response to the last
operation command has not
been returned.

Check the response to the
last operation command,
then execute the operation
command again.

Timeout error

0xBB

0x00

A response has not been
returned for more than 5
seconds after an operation
command is executed.

Turn the power off, check the
connection between the unit
and sensor amplifiers, then
turn the power on again.

Parameter error

0xA0

0x00

Attempting to read
unreadable data.

Specify an appropriate
parameter.

0xA1

0x00

Attempting to write unwritable
data.

0xB0

0x00

The parameter range has
been exceeded.

0xB2

0x00

0xB7

0x00

0xB8

0x00

0xB1

0x04

Attempting to write data with
a size other than 4 bytes.

Access with 4 bytes.

0xB6

0x00

0xB5

0x00

The procedure to read
I&M0 information is
incorrect.

Communication has not
been established.

Read I&M0 information
following the proper
procedure.

Check the configuration
and parameter settings,
then establish
communication to
exchange data.

System error

0xBC

0x00

A system error has occurred.

Turn the power on again. If
the unit does not recover,
please contact your nearest
KEYENCE office (addresses
are listed at the back of this
manual).

0xBD

0x00