4 diagnostic function, Slave diagnosis structure, Diagnostic function -10 – KEYENCE DL-PD1 User Manual

Page 34: Slave diagnosis structure -10, Diagnostic function

Advertising
background image

3-10

- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT2) -

Execu

ting Communi

cat
ion

3

3-4

Diagnostic Function

Using the slave diagnostic function of PROFIBUS DP, the information of error caused on
the DL-PD1 or sensor amplifier can be sent to the master via PROFIBUS DP.

Slave diagnosis structure

The frame length of the DL-PD1 slave diagnosis is the maximum of 67 bytes. The slave
diagnosis consists of 6-byte standard diagnosis, 4-byte Identifier-related diagnosis, 9-
byte module status and maximum of 48-byte Channel-related diagnosis. The frame
length of the Channel-related diagnosis changes depending on the number of sensor
amplifiers connected. The minimum length is 3 bytes and the length increases 3 bytes
per sensor amplifier additionally connected.

Also, the diagnostic function can be set to Enable/Disable by slot at the parameter
setting for DL-PD1. When the diagnostic function is set to Disable, the slot information is
deleted from the diagnostic frame.

"Parameterization" (page 3-8)

1
2
3

4

5
6

7

:

10

11

:

19

20

:

67

:

:

:

Octet

Station status 1 to 3

PROFIBUS DP master address

Manufacturer ID

Identifier-related diagnosis
(Error information)

Module status

Channel-related diagnosis
Minimum 3 bytes
3 bytes increase per slot

Standard Diagnosis

Channel-related
Diagnosis