Types of error and error code

For how to read error information using a diagnosis function, refer to "Device maps"
(page 3-18).

Slot

Error code

(DEC)

Description

Solution

0

(DL-PD1)

16

Unassigned ID error

The number of sensor amplifiers increased during
operation. Check the connection with the sensor
amplifier.

17

Start-time Communication error

Check the connection with the sensor amplifier
and cycle the power.

18

Unsupported Sensor Connection
error

There is connected a sensor amplifier of a model
incompatible with the DL-PD1. Connect a sensor
amplifier of a compatible model.

19

Mixed Model error

A foreign sensor amplifier (i.e., one that cannot be
intermixed) is connected. Remove the foreign
sensor amplifier.

20

Start-time Communication error

Check the connection with the sensor amplifier
and cycle the power.

21

Current Limitation error

The current limitation exceeds the allowable
range. Check the allowable range of the number of
the sensor amplifiers.

22

Communication error between
Sensors

An error exists in the communication between
sensor amplifiers. Check the connections of the
sensor amplifiers, and then turn off the power and
back on.

23

Changed Station Address error

The station address was changed during
operation. If it was not an intentional change,
check the correct station address and set.

24 to 31

Reserved for system

00

No error

-

1-15

(Sensor

amplifier)

16

Overcurrent error

Refer to the GT2 series user's manual.

17

Head error

18

EEPROM error

19

Jam check error

20

Self-timing delay error

21

Number-of-units error

22

Calculation error

23

Calculation-only mode error

24 to 31

Reserved for system

00

No error

-