Device maps, Device maps -18, Monitor mode – KEYENCE DL-PD1 User Manual

Page 42: Dl-pd1 (slot 0), 5 overview of profibus dp communication, Execu ting communi cat ion, Input

Advertising
background image

3-5

Overview of PROFIBUS DP Communication

3-18

- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT2) -

Execu

ting Communi

cat
ion

3

Device maps

Monitor mode

In the monitor mode, the following functions can be performed.

Reading the control output to the sensor amplifiers:

"Parameterization" (page 3-8)

External input request to the sensor amplifiers:

"Parameterization" (page 3-8)

Reading the comparator value:

"Parameterization" (page 3-8)

Reading the error status:

"Parameterization" (page 3-8)

DL-PD1 (Slot 0)

Input

Octet

Bit

Function name

Description

Value

0

0

Reserved for system

-

-

1

Reserved for system

-

-

2

Comparator value property

Stores the comparator value status.

0: Normal
1: Disabled status
“----”, “FFFF”, or “-FFFF”

3

Reserved for system

-

-

4

Reserved for system

-

-

5

Sensor ready

It is output when PROFIBUS DP
communication is established.

0: Starting
1: Ready

6

Reserved for system

-

-

7

Error status

Stores the error status of the sensor
amplifiers.

"Types of error and error code"

(page 4-3)

0: No error occurred.
1: Error occurred.

1

0

External input response 1

Stores the external input response
to the sensor amplifier.

0: No input
1: Input reception

1

External input response 2

Stores the external input response
to the sensor amplifier.

0: No input
1: Input reception

2

External input response 3

Stores the external input response
to the sensor amplifier.

0: No input
1: Input reception

3

External input response 4

Stores the external input response
to the sensor amplifier.

0: No input
1: Input reception

4

Reserved for system

-

-

5

Reserved for system

-

-

6

Reserved for system

-

-

7

Reserved for system

-

-