Vender parameter, 3 parameterization, Execu ting communi cat ion – KEYENCE DL-PD1 User Manual

Page 33: Unique parameters for dl-pd1

Advertising
background image

3-3

Parameterization

3-9

- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT2) -

Execu

ting Communi

cat
ion

3

Vender parameter

Unique parameters for DL-PD1

: Default value

Octet

Name

Description

Value

11

Reserved

-

1 (fixed)

12

Data Format

Selects data storage format when
sending/receiving 2 bytes or larger data.

0: Intel (little endian)
1: Motorola (big endian) 

13

Extended Diagnosis

Selects whether to include information
other than standard diagnosis into slave
diagnosis.

0: Disable
1: Enable 

14

Indicate error slot
[Sensor Amplifier]

Selects the sensor amplifier as a target
for slave diagnosis. If the sensor
amplifier is set as a target, set bit
corresponding to the slot number.

"Diagnostic Function" (page 3-10)

(Default value: 1111 1111

B

)

15

(Default value: 1111 1110

B

)

Slot 0 is fixed to 0.

16

Indicate warning slot
[Sensor Amplifier]

Selects whether to include warning
information into slave diagnosis
information. If so, set bit corresponding
to the slot number.

(Default value: 0)

17

(Default value: 0)

18

Reserved

-

0 (fixed)

bit

7

:

:

0

Slot 15

Slot 8

bit

7

:

:

0

Slot 7

Slot 0

bit

7

:

:

0

Slot 15

Slot 8

bit

7

:

:

0

Slot 7

Slot 0