Profibus dp master address, Manufacturer id, Profibus dp master address -12 manufacturer id -12 – KEYENCE DL-PD1 User Manual

Page 36: Station status 2, Station status 3, 4 diagnostic function, Execu ting communi cat ion, The parameter is not assigned

Advertising
background image

3-4

Diagnostic Function

3-12

- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT2) -

Execu

ting Communi

cat
ion

3

Station status 2

*1 This bit is updated only when another diagnosis message is updated, too.

Station status 3

PROFIBUS DP master address

The PROFIBUS address of PROFIBUS DP master is stored in Octet 4. When the value
is FF

H

, the parameter is not assigned.

Manufacturer ID

Codes unique for the DL-PD1 status are stored in Octet 5 and 6.

Octet

bit

Content

2

0

Set the DL-PD1 parameter again.

1

A diagnosis message is present. The DP slave does not operate until the problem is eliminated.
(Static diagnosis message)

2

(1 fixed)

3

The watchdog is enabled.

4

The DP slave is in "FREEZE" state.

*1

5

The DP slave is in "SYNC" state.

*1

6

(0 fixed)

7

The DP slave is disabled.

Octet

bit

Content

3

0

:

6

(0 fixed)

7

Diagnosis messages exceed the maximum amount that can be stored. Increase the storing memory.

Octet

Content

Value

5

Manufacturer ID is stored. (high byte)

0D

H

6

Manufacturer ID is stored. (low byte)

FD

H