Using the optional DI signal

Remote operations Гог the totalizer and pulse output can be conducted using the optional DT
signal. The rollowijtg functions in the table can be performed. See 8.2.9 “Digital VO” to
select these lunciions.

Dl .signal(normal converter, detective level: H level)

Digital input (Dl)
Functions

1Л voltage level

Totalizer and pulse output

Totalizer

Llevel

Stops the totalizer and the pulse output.

Siarl/Siop

H level

Starts the totalizer and the pulse output.

Totalizer

И level

Stops and clears (resets) the totalizer.

Reset/Start

Í. level

Starts the totalizer and the puhe output.

* In case of the converter for special specifications (refer to 7.3.3 “Converter for Spcciai

specifications"), you can select Digital Input Detective Level (Only for Counter Control).

For detail, see 8.2,19 “Digital Inpu: Detective LevcF'

“Select H level(l:H LEVFd.) ; refer lo upper table,“ Dl signal(normal converter,

deteclive kvd;

H

level)”.

“Select L level(0:L LFVEL) : refer to under table,“ Dl signal(converter for

special specifications detective level: L level)“,

1)1 signalfconvcrter for special specifications, detective level: L level)

Digital input (Dl)

Functions

Dl voltage level

Totalizer and pulse output

Totalizer

L level

Starts ihe totalizer and the puke output.

Start/Slop

J1 level

Stops the totalizer and the pulse output.

Totalizer

11 level

Starts the totalizer and the pulse output.

Reset/Starl

i.kvel

Stops and clears (resets) the totalizer.