S 2 A 4 Rate*Of-Change Limit

The riite-of-changc limit is used to eliminate high dectricftl noise contained in the process

flow i^ignal.

To check electrical noise, two parameters arc defined: rate-of-change limit (set in percent

value of the span) and control limit rime (set in units of seconds). Normally ihe flowmeter

produces the analog output signal by sampling the flow rale signal at 1/24 (or 1/12) of a

second sampling rate. If the sampled value exceeds the set rate-of-ehange limit value based

on the averaged flow rate value up until Ihc sampled lime, the system will reject that

sampled value and instead the averaged value including Ihe ratc-of-changc limit value in

place of the rejected sampled value will be output. However, if the limit-exceeding sampled

value cominues for the same flow direction for more than the preset control limit lime, that

data will be used as the oulpul signal The setting ranges for these two parameters are as

follows:

* Rate-of-chtmge limit

0 to 30 %/sampling rale (in increments of 0.3 %)

Where the sampling rate is either 1/24,1/12 or 1/6 of a second depending on the

excitation frequency as shown below:

Excitation frequency

Sampling rale

24 Hz

1/24 sec

12IIzor6Hz

1/12 sec

- Control

limit time:

Ü to 20 sec (in increments of 1 second)

NOTE

If ‘*0’’ is sel in either of these parameters, the rate-of-change limit function is disabled.

Proceed as follows to check or change the raie-of-change limit value and the control limit

lime.

-