Modular Block System: Burner Management

6-61

P+:

Gas pressure monitor
P+ = 1: Gas pressure present
P+ = 0: No pressure or incorrect pressure

P-:

Air pressure monitor
P- = 1: Air pressure present
P- = 0: No pressure or incorrect pressure

T_V:

Monitoring time for checking the valves' seals (if valves are
seated)
In this time the monitoring process must be carried out at least
once, otherwise it will lead to a shutdown.
Permitted value range: - 32768 ... 32767
Time base: 10 s
T_V > 0: monitoring the seal check is carried out
T_V

1: monitoring the seal check is not be carried out

(Note: time monitoring for calling up the checking process can
be used, for example, in plants with 72-hour operation).

T:

Timer which measures the time

T_V

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is error-free
(refer also to Programming Guidelines)

RDY:

Sequence output
If a block step is activated, the corresponding bit is set in the
output parameter

RDY.

VAV1:

VAV1 = 1: open safety valve

VAV3:

VAV3 = 1: open main valve

VAV4:

VAV4 = 1: open ventilation valve

GP+:

GP+ = 1: pressure monitor for P+ monitor (gas pressure)

GP-:

GP- = 1: pressure monitor for P- monitor (air pressure)

Function

Monitoring that the safety valve (VAV1), the main valve (VAV3) and the
ventilation valve (VAV4) are seated correctly.

See the diagram on the next

page.