Programming guidelines, Standard function blocks sb149 – Pilz PSS SB FT, Basic license User Manual

Page 48

Advertising
background image

6-4

Modular Block System: Burner Management

Standard Function Blocks

SB149

Programming guidelines

STEP
The operand for the input parameter

STEP of SB149 must also be

assigned to the output parameter

STEP from SB152 and also to the

input parameter

STEP of SB157, if SB157 is used. This will enable the

individual steps of the sequence to reset during burner start-up.

The operand for the parameter

STEP has the value 1 for the duration of

a cycle when a positive edge of the ENBL of SB152 is detected.

If several burners are operated with one PSS, each burner must be
assigned its own STEP operand. This enables the burners to be
controlled and monitored independently.

Example:

SB149

STEP

X - RDY
X - COND

M

70.00

.Burner 1

- X - STEP

B - W_BA

W - W_V

Z - W_T

B - D_BA

W - D_V

Z - D_T

NEXT - X

W_E - X

D_E - X

SB157

IGNI_TRY

B - SSNR
X - SyOK
X - BIT0
X - BIT3
X - FLAs
B - ITRY

M

70.00

.Burner 1

- X - STEP

W - T_V

Z - T

RDY - X