Modular Block System: Burner Management

Standard Function Blocks

SB151: Transient suppression

Block header

Input parameters

•

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further infotmation about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present

•

S1:

N/C contact to be monitored (check with test pulse)

•

BASE:

Setting the time base
BASE = M110.00 (RLO = 0): time base of 50 ms, multiplied by
T_V gives a possible range of 50 ms to 27.3 min
BASE = M110.01 (RLO = 1): time base of 100 ms, multiplied
by

T_V gives a possible time range of 100 ms to 54,6 min

•

T_V:

Multiplier for

BASE, to determine the length of time the enable

signal should be delayed
Permitted value range: 1 ... 32767

•

T:

Timer, which measures the set time

•

AuSt:

Automatic start (reset)
AuSt = M110.01 (RLO =1): automatic start (without reset)
AuSt = M110.00 (RLO =0): no automatic start

•

RSET:

Reset button (N/O)

SB151

BridgedS

B - SSNR
X - S1
X - BASE

W - T_V

Z - T

X - AuSt
X - RSET

ENBL - X