Modular Block System: Burner Management

6-101

Programming guidelines

ENBL

The negative edge of the enable

ENBL from SB159 must set a flag to “0”

for the duration of one PSS-cycle. This pulse flag must be supplied to the
AND-operation before the global input

ERR or to the AND-operation

before the global input

CHAI from SB152 “Burner: Start and operator

elements”. The decision to use

ERR or CHAI depends on the user and

the respective standards regarding error reaction.

ERR: If an error is present a controlled shutdown is carried out, when

AuSt = 1 with restart

CHAI: If an error occurs a safety shutdown is carried out.

A programming example can be found in Chapter 8 under “Managing
enables”.

Driving the main valve VAV3

The situation could arise where the main valve VAV3 is driven
simultaneously by SB156 “Tightness control” and SB159 “Run”.

Aid: Assign different flags to the output parameter

VAV3 from SB156 and

for VAV3 and the output parameter

VAV3 from SB159 for VAV3. After

calling up the SB, perform an OR-operation on both flags and drive the
corresponding peripheral output with the result of this logic operation.

Example:

SB156

TIGHT_C

B - SSNR
B - NEXT
X - SyOK
X - V4?
X - P+
X - P-

W - T_V

Z - T

ENBL - X

RDY - B

VAV1 - X
VAV3 - X - M

90.00

.main valve SB156

VAV4 - X

GP+ - X

GP- - X