Modular Block System: Burner Management

Temporary flag range in MBS blocks

Internally, MBS blocks use the flags in the range M 64.00 ... M69.31 as
temporary flags.

NOTICE
We recommend the following:

• Do not use flags from the temporary flag range for your own applications.

Malfunctions may occur if you use the temporary flag range M64.00 ...
M69.31 for your own applications.

• If it is absolutely necessary to use this flag range, under no

circumstances should you use the flags:
- in alarm OBs
- as input parameters for standard function blocks
- as output parameters for standard function blocks
- as global parameters

Output parameter ENBL

Many standard function blocks have an enable output ENBL. This output
parameter indicates the enable status of a standard function block. The
enable status results from the standard function block’s check of the
inputs.

ENBL

= 1: No error found,

the function is enabled

ENBL

= 0: An error has been found,

the function is not enabled.

Advertising