Error messages – Pilz PSS SB FT, Basic license User Manual

Page 75

Advertising
background image

Modular Block System: Burner Management

6-31

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).

• Error messages in DB015

- Bit 00: Flame signal sequence interrupted: fault lock-out occurs

Remedy: First press the reset button (

RSET) and then the start

button (

STRT)

- Bit 01: Safety sequence is interrupted: controlled shutdown occurs

Remedy: First press the reset button (

RSET) a then the start

button (

STRT).

- Bit 02: Error sequence is interrupted: controlled shutdown occurs

Remedy: If

AuSt = 1, wait until the error sequence is

inactiveagain, otherwise press the reset button (

RSET) and

then press the start button (

STRT).

- Bit 03: Monitor sequence is interrupted: controlled shutdown occurs

Remedy: If

AuSt = 1, wait until the monitor sequence is inactive

again, otherwise press the reset button (

RSET) and then the

start button (

STRT).

- Bit 04: Minimum air pressure at start-up was not achieved after step

“Build up minimum air pressure”: safety shutdown occurs
Remedy: First press the reset button (

RSET) and then the start

button (

STRT).

- Bit 05: Below minimum air pressure during operation: controlled

shutdown occurs
Remedy: If

AuSt = 1, wait for the air pressure monitor to signal

minimum air pressure, otherwise press the reset button (

RSET)

and then the start button (

STRT).

- Bit 06: Stop triggered by pressing the stop button

Remedy: Press the start button (

STRT).

- Bit 07: Flame signal sequence is interrupted: controlled shutdown

occurs
Remedy: If

AuSt = 1, wait for the flame signal sequence to be

inactive again, otherwise press the reset button (

RSET) and