Standard function blocks, Sb156 – Pilz PSS SB FT, Basic license User Manual

Page 110

Advertising
background image

6-66

Modular Block System: Burner Management

Standard Function Blocks

• Sequence for seal check

-

NEXT = 0:

Seal check was not activated

° Enable

→

ENBL = 1

° Seal check step not active

→

RDY = 0

° Safety valve closed

→

VAV1 = 0

° Main valve closed

→

VAV3 = 0

° Exhaust valve closed

→

VAV4 = 0

° Test output

→

GP- = 0

° Test output

→

GP+ = 0

-

NEXT, Bit 00 = 1: Ventilate

° Enable

→

ENBL = 1

° Seal check step 1 is active

→

RDY, Bit 00 = 1

° Safety valve closed

→

VAV1 = 0,

if

V4? = 0: open main valve

→

VAV3 = 1

if

V4? = 1: open ventilation valve

→

VAV4 = 1

° Test output

→

GP- = 0

° Test output

→

GP+ = 0

-

NEXT, Bit 01 = 1: Testing for air pressure

° Enable

→

ENBL = 1

° Seal check step 2 is active

→

RDY, Bit 01 = 1

° Safety valve closed

→

VAV1 = 0

° Main valve closed

→

VAV3 = 0

° Exhaust valve closed

→

VAV4 = 0

° Test output

→

GP- = 1

° Test output

→

GP+ = 0

-

NEXT, Bit 02 = 1: Filling

° Enable

→

ENBL = 1

° Seal check step 3 is active

→

RDY, Bit 02 = 1

SB156

Advertising
This manual is related to the following products: