Modular Block System: Burner Management

6-25

Timing diagrams

Setting the

ENBL output automatically when the signal is recovered

Setting the

ENBL output after a reset when the signal is recovered

A failure of

S1 for a time less than the block set time means the

ENBL output does not switch to "0".
Only if

S1 drops out for a longer period of time will the ENBL output

reset.

The

ENBL output is set immediately without the

need for intervention.

A failure of

S1 for a length of time less than the block set time

means the

ENBL output does not switch to "0".

Only if

S1 fails for a longer period of time will the ENBL output

reset.

With signal recovery the

ENBL output

is set only after a reset signal.