Blocks required, Standard function blocks, Sb153 – Pilz PSS SB FT, Basic license User Manual

Page 86

Advertising
background image

6-42

Modular Block System: Burner Management

Standard Function Blocks

- Bit 02: Switch time for the change in position is exceeded.

Remedy: check the switch time

T_V for the contact(s) and reset

the error.

- Bit 03:

DirO and DirC driven simultaneously
Remedy: Only drive in one direction and reset the error. If
neither limit switch is operated, the drive direction must be re-
selected.

- Bit 04: Feasibility check: neither limit switch operated.

Remedy: Check contacts and reset the error. Subsequently if
neither limit switch is operated, the drive direction must be re-
selected.

- Bit 05: Feasibility check: both limit switches operated.

Remedy: check contacts and reset error.

- Bit 06: Reset button not operated

Remedy: Press reset button

- Bit 07: A new drive direction selected

Remedy: Create a positve edge at

DirC or DirO

• Error messages on the CPU-display

- E001: Parameter errors

The

SSNR does not lie withn the limits 1 ... 200. The incorrect

SSNR is stated in DB015/DW0000 (refer also to the section
“Administration data blocks DB015, DB016 and DB017 in
chapter 5).

- E007: Invalid time value for

T_V

Blocks required

• DB002:

Will be made available when the configurator is called up

• DB015:

Administration data block
DB015 must consist of its totla length of 1024 data words and
have Read/Write status (see the section “Administration data
blocks DB015, DB016 and DB017” in chapter 5).

• OB101:

To call up SB153

SB153