Modular Block System: Burner Management

SB152: Burner: start and operator elements

SB152 is used to control the burner start and monitor the burner.
Use SB152 to:

• Carry out a delayed start after the controller has started

• Carry out a restart after a controlled shutdown

• Evaluate the reset, start and stop button

• Monitor the air pressure monitor

• Monitor the flames (pilot and main flame)

• Monitor the global messages from the error, monitor and safety

sequences and to carry out a controlled shutdown or safety lockout.

If the safety sequence is interrupted, the error must always be rectified,
followed by a manual reset via the reset button (

RSET) and start button

(

STRT). The block enable ENBL will only be issued when the safety

sequence is no longer interrupted. .

NOTICE
Error reaction is the sole responsibility of the user. All safety-related
aspects must be taken into account when selecting the elements for the
error and safety sequences!

SB153: Control and position monitoring of flaps

SB153 monitors the status of a flap. It opens and closes the flap after the
corresponding input prompt, monitors the direction of a positional change
and checks the reaction time.
The contact bounce time lasts for one cycle, if a change in position occurs.